BEST Energy Kenya measured total harmonic distortion (THD) of 20–65% on several systems at Saj Ceramics in Kenya — far above the 5% limit set by IEEE 519 — causing power losses and lower efficiency. Denka® harmonic plates were installed on 3 October 2023, and THD was compared for 10–19 September (before) and 8–17 October (after).
Results
- Glaze Prep Mill 8: THD from 24.52% to 9.76%
- Gasifier booster pumps: 64.89% to 54.11%
- Solar: 51.37% to 47.73%
- Offloading zone: 50.12% to 47.97%
Impact report by BEST Energy Kenya, 23 October 2023.